14 SEER / 95% AFUE
SINGLE PACKAGE GAS HEATING / ELECTRIC COOLING
R8HE / PPG3HE SERIES
INSTALLATION INSTRUCTIONS
WARNING / AVERTISSEMENT
FIRE OR EXPLOSION HAZARD
•Failureto followsafety warnings exactly
couldresultinseriousinjuryorproperty
damage.
•Installationandservicemustbeperformed
byaqualiedinstaller,serviceagencyor
thegassupplier.
•Do not store or use gasoline or other
ammablevaporsandliquidsinthevicinity
ofthisoranyotherappliance.
WHAT TO DO IF YOU SMELL GAS
•Donottrytolightanyappliance.
•Donottouchanyelectricalswitch;donot
useanyphoneinyourbuilding.
•Leavethebuildingimmediately.
•Immediatelycallyourgassupplierfroma
neighborsphone.Followthegassuppliers
instructions.
•Ifyoucannotreachyourgassupplier,call
theredepartment.
RISQUE D’INCENDIE OU D’ EXPLOSION
•Lenon-respectdesavertissementsdesécurité
pourraitentraînerdesblessuresgraves,lamort
oudesdommagesmatériels.
•L’installationetl’entretiendoiventêtreeffectués
par un installateur qualié, un organisme de
serviceoulefournisseurdegazstaller,service
agencyorthegassupplier.
•Ne pas entreposer ni utiliser de l’essence ni
d’autresvapeursouliquidesinammablesdansle
voisinagedecetappareil,nidetoutautreappareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
•Nepastenterd’allumeraucunappareil.
•Ne toucher à aucun interrupteur électrique;
n’utiliseraucuntéléphonedanslebâtiment.
•Évacuerl’immeubleimmédiatement.
•Appelerimmédiatementlefournisseurdegazen
employantletéléphoned’unvoisin.Respecterà
lalettrelesinstructionsdufournisseurdegaz.
•Sipersonnenerépond,appelerleservicedes
incendies.
DONOTDESTROY.PLEASEREADCAREFULLY&KEEPINASAFEPLACEFORFUTUREREFERENCE.
HORIZONTAL MOUNT SHOWN
3-PHASE&SINGLEPHASE(REVISIONA)
Zobrazit stránku 0
1 2 3 4 5 6 ... 51 52

Shrnutí obsahu

Strany 1 - WARNING / AVERTISSEMENT

14 SEER / 95% AFUESINGLE PACKAGE GAS HEATING / ELECTRIC COOLINGR8HE / PPG3HE SERIESINSTALLATION INSTRUCTIONS WARNING / AVERTISSEMENTFIRE OR EXPLOSION

Strany 2 - TABLE OF CONTENTS

10Figure4.RefrigerantServicePorts&Air ConditioningCondensateDrainLocationsHIGH SIDELOW SIDECONDENSATEDRAINSecuringScrewsFigure5.Interna

Strany 3

11ELECTRICAL WIRING WARNING:ELECTRICALSHOCK,FIREOREXPLOSION HAZARDFailuretofollowsafetywarningsexactlycouldresultinseriousinjuryorprope

Strany 4 - REQUIREMENTS&CODES

12• All208-240voltunitsareshippedfromthefactorywiredfor 240 volt transformer operation. For 208V operation, remove the lead from the transf

Strany 5

13HeatAnticipatorVerify if the thermostat being used for the installation has a heat anticipator setting. This function allows the thermostat to anti

Strany 6

14air-flow. Verify the selected rise is within the specification shown on the furnace rating label or in the tables.DehumidicationOptionsThe fixed spee

Strany 7

15GASSUPPLY&PIPING WARNING:FIRE OR EXPLOSION HAZARD• Failuretofollowsafetywarningsexactlycouldresultinseriousinjuryorpropertydama

Strany 8 - GroundLevel

16applied on each joint or union using a small paintbrush. If any bubbling is observed, the connection is not sealed adequately and must be retightene

Strany 9

17Table3.ManifoldPressureSetting(inWC)forNaturalGasINPUT(BTUH)GASVALVESETTINGALTITUDE ABOVE SEA LEVELZERO TO 1,9992,00OTO2,999FT3,00OTO3

Strany 10 - Securing

18STARTUP&ADJUSTMENTSPre-StartCheckList√ Verify the unit is level and allows evaporator condensate to drain.√ Verify heat exchanger condensa

Strany 11 - AVERTISSEMENT:

191. Turn ON the manual gas valve, located on the outside of the unit to the ON position.2. Check all gas connections for leaks with a soap and water

Strany 12 - % Voltage Imbalance

2TABLE OF CONTENTSIMPORTANT SAFETY INFORMATION... 3REQUIREMENTS&CODES...

Strany 13 - Toavoidpersonalinjury

20unit data label. To determine the firing rate, follow the stepsbelow:1. Obtain the gas heating value (HHV) from the gas supplier.2. Shut off all oth

Strany 14 - CAUTION:

213. Set the thermostat above room temperature and verify the units operating sequence (page 21). NOTE: The over-temperature limit control should turn

Strany 15

22not close within 12 seconds, the control will display a Pressure Switch Open with Inducer On Fault. If the hall effect sensor switch does not close

Strany 16

23BlockedVent/CondensateDisposalShutDownThe pressure switch is constantly monitored throughout the ignition cycle. After normal operation is est

Strany 17

24local dealer about the availability of maintenance contracts. Routinemaintenanceshouldincludethefollowing: CAUTION:The unit should never be

Strany 18

25CleaningofBurnersIf the burners must be cleaned, follow the steps below.1. Shut off the gas supply to the unit either at the meter or at a manual

Strany 19

26FIGURES&TABLES2513.50161213.3116CGA3/4" NPTFEMALE DRAINCONNECTORBDOWNFLOWSUPPLY DUCTOPENINGDOWNFLOWRETURN DUCTOPENING23.5045.7513.501247.

Strany 20 - Operation

27MODELNUMBERR8HE / PPG3HEUNITWEIGHTSHIPPINGWEIGHTCENTER OF GRAVITY UNITDIMENSIONS(INCHES)A BHEIGHT WITHBASE RAILSHEIGHT WITHOUTBASE RAILSLENGTH WID

Strany 21

28AirowInformationTable8.CoolingAirowSettingsSWITCHSETTINGRECOMMENDEDAIRFLOW(CFM)SWITCHSETTINGRECOMMENDEDAIRFLOW(CFM)5 6 7 85 6 7 80 0 0 02TO

Strany 22

29R8HE/PPG3HE-X24K060XA/-X30K060XA60,000BTUH,30”CABINET,11”X8”BLOWERW-3/4HPECMMOTOR230 VOLT OPERATIONSWITCHSETTINGS0.20 0.30 0.40 0.50

Strany 23

3IMPORTANT SAFETY INFORMATIONPlease read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special

Strany 24

30R8HE/PPG3HE-X36*080(X,XA)80,000BTUH,30”CABINET,11”X8”BLOWERW-1HPECMMOTOR230 VOLT OPERATIONSWITCHSETTINGS0.20 0.30 0.40 0.50 0.60 0.70

Strany 25

31Table12.BlowerPerformance-3.5TonR8HE/PPG3HE-X42K080XA80,000BTUH,34”CABINET,11”X10”BLOWERW-1HPECMMOTOR230 VOLT OPERATIONSWITCH SET

Strany 26 - FIGURES&TABLES

32R8HE-X48*096(X,XA)&R8HE-X60*096(X,XA)96,000BTUH,38”-42”CABINET,11”X10”BLOWERW-1HPECMMOTOR230 VOLT OPERATIONSWITCH SETTINGS0.20 0

Strany 27 - (DOWNFLOW APPLICATION)

33GasInformationTable14.GasPipeCapacitiesCAPACITYOFBLACKIRONGASPIPE(CU.FT.PERHOUR)FORNATURALGAS(SPECIFICGRAVITY-0.60)NOMINAL PIPED

Strany 28 - AirowInformation

34Figure9.GasValveLabelA. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do

Strany 29

35Table16.ElectricalData.SINGLE PHASE MODELSMODELNUMBERR8HE / PPG3HEHEATINGINPUT(BTUH)INDUCERMOTORNOMINALELECTRICALSUPPLY VOLTAGERANGECOMPRESSORFAN

Strany 30

36GREENREDSTATUSNOT USEDTEST PORTBLOWER MOTORRCY1TWINDEHUMW1EXPANSIONPORTCOOLHEATFAN SPEED1 2 345 6 78OFF ONFigure11.FixedSpeedMotorControlBoard

Strany 31

37WIRING DIAGRAM208/230 Volt / 1 Phase / 60 Hz2-5 Ton Package 2 Stage Gas/Single Stage Air Conditioner NOTES:1. Couper le courant avant de faire letre

Strany 32

38WIRING DIAGRAM208/230 Volt / 3 Phase / 60 Hz3-5 Ton Package 2 Stage Gas/Single Stage Air Conditioner NOTES:FIELD WIRINGLEGEND:LOW VOLTAGEHIGH VOLTAG

Strany 33 - Input To Furnace (Btu/hr)

39WIRING DIAGRAM460 Volt / 3 Phase / 60 Hz3-5 Ton Package 2 Stage Gas/Single Stage Air Conditioner NOTES:1. Couper le courant avant de faire letretien

Strany 34 - Figure9.GasValveLabel

4diagram before making any electrical connections to the unit. See the unit wiring label or Figure 13 (page 37), Figure 14 (page 38), & Figure 15

Strany 35 - ElectricalData

40ChargingCharts26028030032034036038040042044046048050080 85 90 95 100 105 110 115 120Liquid Temperature (F)Liquid Pressure (psig)2 TON CHARGING CHAR

Strany 36 - ElectricalDiagrams

4126028030032034036038040042044046048050080 85 90 95 100 105 110 115 120Liquid Temperature (F)Liquid Pressure (psig)3 TON CHARGING CHART60657075Add re

Strany 37 - WIRING DIAGRAM

4228030032034036038040042044046048050080 85 90 95 100 105 110 115 120Liquid Temperature (F)Liquid Pressure (psig)4 TON CHARGING CHART520125130Remove r

Strany 38

43APPENDIXA-HEATEXCHANGERCONDENSATEDRAIN&VENTKIT (HORIZONTALMOUNTAPPLICATIONS) WARNING:ELECTRICALSHOCK,FIREOR EXPLOSION HAZARDFailur

Strany 39

44Preparing the pitAfter pit location has been determined, the condensate drain pit must be prepared for installation of the vertical 2” PVC vent pipe

Strany 40 - 2.5 TON CHARGING CHART

45recommended for areas where temperatures are below 200 F for extended periods of time but is also dependent on the final depth of the trench if the f

Strany 41 - 3 TON CHARGING CHART

46FROSTLINE 3" 2" - 3" ROCK BASEBELOW 2” PVC PIPE12" - 14"OR GREATER 4" - 6" OR DEEPER BACKFILLROCK/DIRTMIXTURERO

Strany 42 - 5 TON CHARGING CHART

47APPENDIXB-HEATEXCHANGERCONDENSATEDRAIN&VENTKIT (ROOFCURBMOUNTAPPLICATIONS) WARNING:ELECTRICALSHOCK,FIREOR EXPLOSION HAZARDFailure

Strany 43

48SettingtheUnitIMPORTANT NOTE:Beforehoistingandsettingtheunitinplace,theshortpieceoffactoryinstalleddrainlinelocatednexttotheun

Strany 44 - READTHISBEFOREYOUDIG!

49ROOF MOUNTED UNIT(ROOF CURB AND ROOF NOT SHOWN)SpringHose Clamp2” PVC x 22.5 Degree Elbow& 1/4” Mesh Screen1/2” ID x 84”Drain HoseFlexible Insul

Strany 45 - Preparing the Trench

5GENERAL INFORMATIONThis Single Package Gas Heating / Electric Cooling Unit is designed for outdoor rooftop or ground level slab installations and can

Strany 48

Specifications & illustrations subject to change without notice or incurring obligations (07/14).709726A (Replaces 7097260)INSTALLATION / PERFORMAN

Strany 49 - ROOF MOUNTED UNIT

6 WARNING:Combustible air must not be drawn from acontaminatedatmosphere.Excessiveexposureto contaminated combustion air will result

Strany 50

7CIRCULATING AIR SUPPLY WARNING:Productsofcombustionmustnotbeallowedtoenterthereturnairductworkorthecirculatingairsupply.Failureto

Strany 51

8ClearancestoCombustibleMaterialsThese units are certified as combination heating and cooling equipment for outdoor rooftop or ground level installa

Strany 52 - ATTENTION INSTALLERS:

9• Securementofthedrainlinetotheinsidesurfaceofthe roof curb is acceptable and should be made in the wood nailer area (top 3.5”) to avoid p

Komentáře k této Příručce

Žádné komentáře