
7
Figure 2
GeneralInformation
WARNING:
Installation methods other than those described
inthefollowingsectionsmustcomplywiththe
National Fuel Gas Code and all applicable local
codesforprovidingsufcientcombustionairto
thefurnace.
Provisions must be made during the installation of this
unit that provide an adequate supply of air for combustion.
• Instructions for determining the adequacy of an
installation can be found in the current revision of the
NFGC(ANSIZ223.1/NFPA54).Consult local codes
forspecialrequirements. These requirements are for
US installations as found in the NFGC.
• TherequirementsinCanada(B149.1)arestructured
differently. Consult with B149.1 and local code officials
for Canadian installations.
WARNING:
Combustion air must not be drawn from a
contaminatedatmosphere.Excessiveexposure
to contaminated combustion air will result in
safetyandperformancerelatedproblems.
To maximize heat exchanger life, the combustion air
must be free of chemicals that can form corrosive acidic
compounds in the combustion gases. The recommended
source of combustion air is to use clean air from outside.
DO NOT place any chemicals with flammable or caustic
vapors or these other corrosive chemicals near the
vent termination:
• Gasoline/Kerosene
• Permanentwavesolutions
• Chlorinatedwaxesandcleaners
• Chlorinebasedswimmingpoolchemicals
• Watersofteningchemicals
• De-icingsaltsorchemicals
• Carbontetrachloride
• Halogentyperefrigerants
• Cleaningsolvents
• Cements,glues,paintremovers,varnishes,etc.
• Hydrochloricacid
• Masonryacidwashingmaterials
• PlumbingStack
Air openings in the door of the unit, warm air registers,
and return air grilles must never be restricted. If the unit
does not receive an adequate supply of air for combustion,
the flame roll-out control located above the burners will
open, turning off the gas supply to the burners. This safety
device is a manually reset switch.
IMPORTANT NOTE
DONOTinstalljumperwiresacrossthiscontroltodefeat
itsfunctionorresetthecontrolwithoutidentifyingand
correctingthefaultcondition.
If this control must be replaced, use only factory authorized
replacement parts. See the Replacement Parts List on
page 25.
Vent Termination
This unit has been equipped with an integral venting
system and designed to operate only with this venting
system. No additional venting shall be used. This unit
must be vented to the outdoors.
WARNING:
This unit is intended for outdoor installation
only. Do not vent the unit through a conventional
venting system.
A vent cover assembly has been supplied with the unit
and can be found secured to the gas controls within
the control area of this unit. Figure 2 shows the proper
installation of the vent cover assembly over the vent outlet
on the exterior of the corner panel. The fasteners used to
secure the vent cover assembly have been included in
the owner’s package. The vent cover assembly must
beinstalledtoassureproperoperationoftheunit.
The following list summarizes the requirements for the
locationoftheventsystemtermination:
• Thelocationoftheventterminationmustbeconsistent
withtheNationalFuelGasCode(ANSIZ223.1)orCAN/
CGA-B149 Installation Codes.
• The vent terminationmust belocatedat least4feet
horizontally from any electric meters, gas meters,
regulators, and relief equipment.
• The vent terminationmust belocatedat least3feet
above any forced air inlet located within 10 feet.
• The vent terminationmust belocatedat least4feet
below, 4 feet horizontally from, or 1 foot above any
door, window, or gravity air inlet into any building.
• The vent terminationmust belocatedat least1foot
above grade.
• Theunitshouldbeinstalledinawaythatpreventsany
obstruction of the vent termination during accumulating
snow.
Figure 2. Vent Assembly
Komentáře k této Příručce