Reznor MAPS - A,B,C Users Manual Uživatelský manuál Strana 12

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 40
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 11
Form O-MAPSIII&IV Cabinets A/B/C, Page 12
3.0 Maintenance/Service Procedures (cont'd)
3.6 Compressor Operation, Maintenance, and Replacement (cont'd)
208-240/3/60 480/3/60 575/3/60
Compressor
Crankcase
Heater P/N
Compressor
Crankcase
Heater P/N
Compressor
Crankcase
Heater P/N
Model P/N Model P/N Model P/N
ZP24K5E 235095 216434 ZP24K5E 235097 216436 ZP24K5E 235099 216437
ZP36K5E 235096 216398 ZP36K5E 235098 216400 ZP36K5E 235100 216401
ZP54K5E 235008 216398 ZP54K5E 235012 216400 ZP54K5E 235016 216401
ZP57K3E 216686 216398 ZP57K3E 216687 216400 ZP57K3E 216688 216401
ZP72KCE 235009 216398 ZP72KCE 235013 216400 ZP72KCE 235018 216401
ZP83KCE 216689 216398 ZP83KCE 216690 216400 ZP83KCE 216691 216401
ZP137KCE 235010 216398 ZP137KCE 235014 216404 ZP137KCE 235019 216405
ZPT144KCE 235011 216398 ZPT144KCE 235015 216400 ZPT144KCE 235020 216401
ZP154KCE 220260 216402 ZP154KCE 220261 216404 ZP154KCE 220262 216405
Compressors and Crankcase Heater P/N's by Voltage on MAPS
®
III Models
208-240/3/60 480/3/60 575/3/60
Compressor
Crankcase
Heater P/N
Compressor
Crankcase
Heater P/N
Compressor
Crankcase
Heater P/N
Model P/N Model P/N Model P/N
ZP24K5E 235095 216434 ZP24K5E 235097 216436 ZP24K5E 235099 216437
ZP36K5E 235096 216394 ZP36K5E 235098 216396 ZP36K5E 235100 216397
ZP54K5E 235008 216394 ZP54K5E 235012 216396 ZP54K5E 235016 216397
ZP57K3E 216686 216398 ZP57K3E 216687 216400 ZP57K3E 216688 216401
ZP61KCE 261235 216398 ZP61KCE 261236 216400 ZP72KCE 235018 216401
*ZPD61KCE 261145 216398 *ZPD61KCE 261146 216400 ZP83KCE 216691 216401
ZP72KCE 235009 216398 ZP72KCE 235013 216400 *ZPD83KCE 261149 216401
ZP83KCE 216689 216398 ZP83KCE 216690 216400 ZP137KCE 235019 216405
*ZPD83KCE 261147 216398 *ZPD83KCE 261148 216400 *ZPD137KCE 261155 216405
ZP137KCE 235010 216402 ZP137KCE 235014 216404 *ZPD61KCE 268531 216401
*ZPD137KCE 261153 216402 *ZPD137KCE 261154 216404 ZP61KCE 268532 216401
ZP154KCE 220260 216402 ZP154KCE 220261 216404 *ZPDT14MCE 268533 216401
*ZPDT14MCE 262656 (2)216398 *ZPDT14MCE 262657 (2)216400 * Modulating capacity compressor
Compressor and Crankcase Heater P/N's by Voltage on MAPS
®
IV Models
Modulating Cooling -
MAPS
®
IV Models
MAPS
®
IV units are equipped with a modulating capacity compressor and a digital con-
troller to provide cooling modulation. The digital controller in the control compartment
(See FIGURE 1, page 5) is the electronic interface between the compressor and the
system controller. The compressor controller is connected to the unit controller to pro-
vide protection and diagnostics for modulating compressor operation.
After a compressor shutdown, a two-minute anti-short cycle timer in the compressor
controller delays the compressor restart. The unit controller has a ve-minute compres-
sor on/off time. The delay times are concurrent so total delay time is ve minutes.
Alarm Light
(Red LED) - See
Paragraph 7.2.
Compressor
Modualting
Solenoid Valve
Energized Light
(Yellow LED)
Power Light
(Green LED)
FIGURE 5 - Compressor Digital Controller
located in the control compartment
interfaces the modulating capacity
compressor with the unit controller.
LED
Color
LED
State
Indicates
Green Solid
Power (24VAC present at power
terminals)
Green Flashing Anti-short cycle timer is active
Yellow Solid
Unloader (Solenoid valve is
energized; compressor capacity is 0.)
Red Not lit No abnormal operation alerts
NOTE: See Troubleshooting, Paragraph 7.2.
NOTE: To identify MAPS
®
IV
Models, see Paragraph 1.0.