Form I-CAUA, P/N 164771 R8, Page 24
6.3 Inlet Air
7) Vent Terminal (Pipe and Vent Cap) (cont'd)
6.0 Mechanical
(cont'd)
6.2 Venting and
Combustion Air
(cont'd)
6.2.2 Venting and Combustion Air Requirements for Power Vent
Drawing Combustion Air from THE INSIDE SPACE and Venting
Flue Products to the Outdoors (cont'd)
Inlet air ductwork is required unless equipped with inlet base Option AVA2. Filters
are recommended when a cooling coil is part of the installation. Inlet air may be 100%
return air, a mixture of return and outside air (air entering the blower must be 35°F or
higher unless equipped with makeup air Option AD4), or 100% outside air if equipped
with makeup air Option AD4.
TABLE 15 - Inlet Air
Opening Dimensions
Inlet Air Opening Dimensions
Sizes
150, 200 250, 300 350, 400
inches mm inches mm inches mm
Without Optional Filter or Mixing Cabinet (actual cutout opening on heater)
Right Side 31 x 16 787 x 406 31 x 16 787 x 406 44 x 16 1118 x 406
Left Side 31 x 16 787 x 406 31 x 16 787 x 406 44 x 16 1118 x 406
Rear 33 x 16 838 x 406 45 x 16 1143 x 406 45 x 16 1143 x 406
Bottom 25-1/2 x 32 648 x 813 37-1/2 x 32 953 x 813 37-1/2 x 46 953 x 1168
With Optional Side or Rear Filter Cabinet (duct opening in top or rear of cabinet)
Attached to Heater Side 32 x 16 813 x 406 32 x 16 313 x 406 45-1/8 x 16 1146 x 406
Attached to Heater Rear 32 x 16 813 x 406 45-1/8 x 16 1146 x 406 45-1/8 x 16 1146 x 406
With Optional Bottom Filter Cabinet (duct opening in bottom of cabinet)
Under Heater 25-1/2 x 32 618 x 813 37-1/2 x 32 953 x 813 37-1/2 x 46 953 x 1168
With Optional Mixing Box (duct opening in top, bottom, or rear of cabinet)
Attached to Heater Rear 22 x 19-1/2 578 x 495
36-1/2 x
19-1/2
927 x 495
36-1/2 x
19-1/2
927 x 495
The location of the inlet air duct connection depends on the installation. Corner indica-
tors for the opening are provided on the right side, the left side, the rear, and the bottom
of the heater. (See Dimensions in FIGURE 1, page 5.) Determine where the inlet air
opening(s) should be and cut out using tin snips or aviation shears.
CAUTION: The cut edges of the metal will be sharp.
Inlet Air Ductwork
If installing an optional lter or lter/mixing cabinet shipped with the heater, attach the
cabinet at the "cutout" opening.
Attach the ductwork to the heater or to the inlet cabinet.
FIGURE 18 - Vertical Vent Terminals
Single-Wall Vent Run and Single-Wall Terminal
Single-Wall Vent Run and Double-Wall Terminal
NOTE: Drawings are not proportional; read all measurements.
Vertical Vent Terminals